SINGLE-PHASE NETWORK ANALYSER – V/I CONVERTER

Single-phase network analyser, voltage-current converter 1000 VDC/600 VAC and 0-10 A AC/DC. Measurements: Irms, Vrms, Watt, Var, Frequency, Cosφ, Energy, THD. Min and max values of all the RMS measurements.

USB configurable, DIN rail mounting, input with 4 kV galvanic isolation, universal power supply AC/DC, programmable alarm contact, RS485 Modbus and analogue output.
Data logging function which saves data to a USB pen drive, data are downloaded in .csv format (and can be imported directly into Excel) with date and time (built-in RTC Real Time Clock).

 

VOLTAGE  Up to 1000 VDC / 600 VAC fully configurable via USB;
CURRENT  Up to 10 A AC/DC direct connection (more using external CT).
CURRENT  0…20 mA programmable, maximum load 600 ohm;
VOLTAGE  0…10 V programmable, minimum load resistance 2 kOhm.
RS485 MODBUS  bus connection on the bottom of the module or terminal, dip-switch for setting address and baudrate.
DRY CONTACT  Optomos contact, programmable NO/NC, programmable alarm contact on parameter chosen through the FACILE QA-POWER-M software

 

MAIN FEATURES:

POWER SUPPLY  10…40 VDC, 20-28 VAC, 50-60 Hz
ABSORPTION   Maximum 2.5 VA
DEGREE OF PROTECTION  IP20
ACCURACY   0.5% FS
MEASUREMENTS  Irms, Vrms, Watt, Var, Va, Vpk, Ipk, Frequency, Cosφ, Bidirectional energy, THD
WORKING FREQUENCY  DC or 1…400 Hz
ISOLATION  4 kV input, 1.5 kV between output, RS485 and power supply.
DIN RAIL MOUNTING  Ready for DIN rail mounting, removable terminals, RS485 connection and power supply on the bottom of the module through T-BUS connector (not included).
TERMINALS  Removable 5.08 mm
CE STANDARDS  EN61000-6-4/2006 + A1 2011 / EN64000-6-2/2005 / EN61010-1/2010
DIMENSIONS  17.5 x 100 x 112 mm (excluding terminals)
DATA LOGGER  Non-volatile memory. Log on USB On-The-Go port by pen drive. Built-in RTC Real Time Clock to manage date and time.
CONFIGURATION  using free FACILE QA-POWER-M software.